When a FANUC robot displays SRVO-064 PHAL, the controller has detected an abnormal phase condition in the pulses generated by the Pulse Coder.
The Pulse Coder is part of the robot's position feedback system. It provides feedback signals that allow the controller to monitor motor position and movement.
If the controller detects an abnormal pulse phase, it may generate SRVO-064 and prevent normal servo operation.
However, there is an important detail when diagnosing this alarm: SRVO-064 may appear together with other Pulse Coder communication alarms, including DTERR, CRCERR, or STBERR. In these situations, the PHAL alarm may not represent an independent Pulse Coder phase failure.
This guide explains what FANUC SRVO-064 means, how to identify the affected axis, how to interpret related alarms, and when Pulse Coder replacement may be necessary.
SRVO-064 – PHAL Alarm (Pulse Coder Phase Error)
According to FANUC controller maintenance documentation, this alarm occurs when the phase of the pulses generated in the Pulse Coder is abnormal.
The Pulse Coder is used to provide position feedback from the robot's servo motor to the controller.
The controller relies on this feedback to determine motor position and movement. When the pulse phase is detected as abnormal, the controller reports SRVO-064 for the affected axis.
The alarm message also identifies the relevant robot group and axis.
For example:
Group: Identifies the robot or motion group.
Axis: Identifies the affected axis within that group.
This information is important because it helps maintenance personnel locate the affected motor and its associated Pulse Coder.
A FANUC Pulse Coder is a position feedback device associated with the servo motor.
Its main functions include:
Generating position-related feedback signals.
Providing motor position information to the controller.
Supporting servo control and position monitoring.
Enabling the controller to track motor movement.
A Pulse Coder problem can therefore affect the controller's ability to correctly interpret motor position.
Although the terms Pulse Coder and Encoder are sometimes used interchangeably in industrial automation discussions, use the exact component terminology and part number when identifying FANUC replacement parts.
SRVO-064 specifically identifies an abnormal pulse phase condition. It should not automatically be treated as a generic encoder cable failure.
The following conditions are important when investigating the alarm.
The most direct explanation is that the Pulse Coder is generating an abnormal pulse phase.
If the Pulse Coder itself is defective, the controller may be unable to receive valid position feedback.
The FANUC maintenance procedure for applicable controller generations lists replacement of the affected Pulse Coder as the corrective action.
SRVO-064 may appear together with other Pulse Coder-related alarms.
FANUC documentation specifically notes that PHAL may accompany:
When these alarms occur together, the PHAL alarm may not represent an actual independent phase error.
This is an important diagnostic distinction.
Do not immediately replace the Pulse Coder based only on SRVO-064 without reviewing the complete alarm history and identifying any accompanying alarms.
If SRVO-064 remains active after the related alarm conditions have been investigated, the affected Pulse Coder requires further diagnosis.
The applicable FANUC maintenance procedure should be followed to determine whether the Pulse Coder needs replacement.
Do not assume that the servo amplifier, robot connection cable, or encoder cable is defective without supporting diagnostic evidence.
A structured diagnostic process helps prevent unnecessary replacement of expensive servo components.
Open the FANUC alarm screen and record the complete SRVO-064 message.
Pay attention to:
Alarm code: SRVO-064.
Alarm description: PHAL.
Group number.
Axis number.
Time when the alarm occurred.
The affected axis identifies which motor and Pulse Coder should be investigated.
Do not assume that the alarm affects the entire robot. It may be associated with one specific axis.
Check whether other servo or Pulse Coder alarms appeared at the same time.
Pay particular attention to:
| Alarm Code | Description | Diagnostic Significance |
|---|---|---|
| SRVO-064 | PHAL | Abnormal Pulse Coder pulse phase |
| SRVO-068 | DTERR | Pulse Coder serial data is not returned correctly |
| SRVO-069 | CRCERR | Pulse Coder serial data communication error |
| SRVO-070 | STBERR | Pulse Coder serial data status error |
If SRVO-068, SRVO-069, or SRVO-070 appears together with SRVO-064, investigate the related communication alarm conditions first.
FANUC documentation warns that SRVO-064 may be generated as an accompanying alarm in these situations, even when no independent PHAL condition exists.
Determine whether SRVO-064:
Appears immediately when the controller starts.
Occurs during robot operation.
Appears together with other Pulse Coder alarms.
Remains after the related alarm conditions have been addressed.
Record the conditions under which the alarm occurs.
Avoid repeatedly resetting the alarm without understanding why it is being generated.
Using the applicable FANUC maintenance procedure, inspect the feedback system associated with the affected axis.
Depending on the controller and robot configuration, qualified maintenance personnel may need to examine:
The affected servo motor and Pulse Coder assembly.
Relevant electrical connections.
The robot connection cable and internal feedback wiring when indicated by related communication alarms.
The servo amplifier interface where the applicable diagnostic procedure requires it.
Before inspecting or disconnecting electrical components, follow the required power isolation procedure and FANUC safety documentation.
Do not disconnect connectors while the equipment is energized.
For SRVO-064, FANUC maintenance documentation lists replacement of the affected Pulse Coder as the corrective action.
If the alarm remains and the diagnostic procedure confirms a Pulse Coder fault, replacement may be required.
However, first distinguish a genuine PHAL condition from an accompanying alarm caused by DTERR, CRCERR, or STBERR.
This prevents replacing a Pulse Coder unnecessarily when the primary problem lies elsewhere in the feedback communication path.
After replacing a Pulse Coder, follow the maintenance and setup procedures specified for the particular robot and controller.
Depending on the hardware configuration and the effect of the repair, position reference verification or mastering may be required.
Do not assume that the same post-replacement procedure applies to every FANUC robot model.
Before returning the robot to production, verify that:
The replacement component is correct.
The alarm has cleared.
Position feedback is functioning correctly.
Any required mastering or position verification has been completed.
The robot passes the applicable operational and safety checks.
Several FANUC alarms involve the Pulse Coder, but they identify different problems.
Understanding these differences helps maintenance personnel select the correct diagnostic procedure.
| Alarm Code | Alarm Name | Main Condition |
|---|---|---|
| SRVO-062 | BZAL | Pulse Coder absolute-position backup battery data is lost |
| SRVO-064 | PHAL | Abnormal phase of pulses generated in the Pulse Coder |
| SRVO-065 | BLAL | Pulse Coder battery voltage is below the specified level |
| SRVO-066 | CSAL | Pulse Coder ROM abnormality |
| SRVO-068 | DTERR | Pulse Coder serial data is not returned correctly |
| SRVO-069 | CRCERR | Pulse Coder serial communication data error |
| SRVO-070 | STBERR | Pulse Coder serial data status error |
These alarms should not be treated as interchangeable encoder faults.
For example:
SRVO-062 and SRVO-065 are associated with Pulse Coder battery conditions.
SRVO-064 identifies an abnormal pulse phase.
SRVO-068, SRVO-069, and SRVO-070 concern Pulse Coder serial data communication or status.
The corrective action depends on the actual alarm and the applicable FANUC controller documentation.
When an encoder-related alarm appears, it is easy to assume that the encoder cable is defective.
However, SRVO-064 specifically identifies an abnormal Pulse Coder pulse phase. It does not automatically confirm a cable failure.
The distinction is important when selecting replacement parts.
| Component | Function | When to Investigate |
|---|---|---|
| Pulse Coder | Generates motor position feedback signals | When a genuine Pulse Coder phase fault is confirmed |
| Encoder / Feedback Cable | Carries feedback signals between relevant components | When cable damage or a communication-path problem is identified |
| Servo Motor | Drives the robot axis and may contain the Pulse Coder assembly | When motor or integrated feedback assembly problems are confirmed |
| Servo Amplifier | Controls the servo motor and processes feedback within the servo system | When the applicable diagnostic procedure indicates an amplifier-side fault |
The exact component arrangement varies by FANUC robot and motor generation.
A Pulse Coder may be integrated into the servo motor assembly or supplied as a separately identifiable component, depending on the design.
Always verify the original part number and replacement configuration before ordering.
If Pulse Coder replacement is required, selecting the correct part is essential.
A visually similar component may not be electrically or mechanically compatible with the original assembly.
Before sourcing a replacement, collect the following information.
Identify the complete FANUC robot model.
Different robot series and motor configurations may use different Pulse Coder assemblies.
Record the axis number reported in the SRVO-064 alarm.
For example, an alarm affecting Axis 1 requires investigation of the feedback system associated with that axis.
Do not order a replacement based only on the robot model without confirming the affected motor and axis.
Record the servo motor model or identification number.
This information helps identify the correct feedback component.
If available, record the complete Pulse Coder or motor assembly part number.
Include all suffixes and revision information.
If the Pulse Coder is integrated into the motor, provide the motor identification label instead.
If the original part number is unclear, provide:
Robot model identification.
Servo motor nameplate.
Pulse Coder label, if separately available.
Connector photos.
Complete SRVO-064 alarm message.
These details help verify the correct replacement component.
The replacement scope depends on the motor design and availability of compatible components.
| Replacement Option | When to Consider It |
|---|---|
| Individual Pulse Coder | The Pulse Coder is separately replaceable and the correct compatible part is available |
| Complete servo motor | The Pulse Coder is integrated into the motor or separate replacement is not supported |
| Feedback cable | Cable damage or a feedback communication problem has been confirmed |
| Servo amplifier | The applicable diagnostic procedure confirms an amplifier-side fault |
Do not replace the complete servo motor or servo amplifier simply because SRVO-064 appears.
First confirm the affected component and the correct replacement configuration.
SRVO-064 PHAL indicates that the phase of the pulses generated in the Pulse Coder is abnormal.
The controller identifies the affected group and axis so maintenance personnel can investigate the corresponding feedback system.
It may indicate a genuine Pulse Coder phase fault. However, FANUC documentation notes that SRVO-064 can also appear together with SRVO-068 DTERR, SRVO-069 CRCERR, or SRVO-070 STBERR, even when no independent PHAL condition exists.
Review the complete alarm history before replacing the Pulse Coder.
SRVO-064 specifically identifies an abnormal Pulse Coder pulse phase, not a confirmed encoder cable failure.
If communication-related alarms appear at the same time, inspect the relevant feedback communication path according to the applicable maintenance procedure.
SRVO-064 identifies an abnormal Pulse Coder pulse phase.
SRVO-068 DTERR indicates that the serial Pulse Coder does not return serial data in response to a request signal.
They represent different alarm conditions and require separate diagnostic procedures.
The required post-replacement procedure depends on the robot and Pulse Coder configuration.
Follow the applicable FANUC maintenance manual to determine whether mastering or position reference verification is required.
In some FANUC motor configurations, the Pulse Coder may be separately replaceable. In others, it may be integrated into the motor assembly.
Confirm the motor model, original part number, and replacement procedure before ordering.
If your FANUC robot displays SRVO-064 PHAL, identifying the affected axis and confirming the actual Pulse Coder condition are the first steps toward a reliable repair.
InRobots supports sourcing FANUC robot feedback components and hard-to-find industrial robot spare parts.
To help identify the correct replacement, provide:
You can also explore our FANUC robot spare parts for related replacement components.
Key components commonly involved in issues and replacements.
No related parts found. Please check available components in our catalog.
{"one"=>"Wählen Sie 2 oder 3 Artikel zum Vergleichen aus", "other"=>"{{ count }} von 3 Elementen ausgewählt"}
Wählen Sie das erste zu vergleichende Element aus
Wählen Sie das zweite zu vergleichende Element aus
Wählen Sie das dritte Element zum Vergleichen aus
Einen Kommentar hinterlassen